4
Devices Required for Constructing a Network
Section 1-2
1-2
Devices Required for Constructing a Network
The basic configuration for an EtherNet/IP System consists of one switching
hub to which nodes are attached in star configuration using twisted-pair cable.
The devices shown in the following table are required to configure a network
with CS1W-EIP21 and CJ1W-EIP21 EtherNet/IP Units or the built-in EtherNet/
IP port in CJ2H-CPU
@@
-EIP/CJ2M-CPU3
@
 CPU Units. 
Recommended 
Switching Hubs
For details on recommended devices for constructing a network, refer to 2-3-1
Recommended Network Devices
.
Note
If a repeater hub is used for EtherNet/IP tag data links (cyclic communica-
tions), the network’s communications load will increase, data collisions will
occur frequently, and stable communications will be impossible. Always use a
switching hub when using tag data links in the network.
1-3
Support Software Required to Construct a Network
This section describes the Support Software that is required to construct an
EtherNet/IP network. Make the tag data link settings and Unit setup settings
for the EtherNet/IP Unit or built-in EtherNet/IP port. Both of these settings are
stored in the EtherNet/IP Unit’s non-volatile memory (See note.). Support
Software is provided for each, as described below. 
Note
Unlike the Ethernet Units, the EtherNet/IP Unit’s TCP/IP settings are not
stored in the CPU Unit’s CPU Bus Unit System Setup Area. The settings are
stored in the EtherNet/IP Unit itself.
Unit Setup: CX-
Programmer
The CX-Programmer is used to set basic parameters, such as the local IP
address of the EtherNet/IP Unit or built-in EtherNet/IP port and the subnet
mask. (The CX-Programmer is included in the CX-One.) 
The CX-Programmer can also be used to check if data I/O is being performed
correctly for tag data links. 
(3) Switching hub
CX-One Support 
Software
(2) Twisted-pair cable
100 m 
max.
(1) CS1W-EIP21 EtherNet/IP 
Unit for CS-series
(1) CJ1W-EIP21 
EtherNet/IP Unit
CS-series 
PLC
CJ-series 
PLC
Ethernet (LAN) port
(1) Built-in EtherNet/IP port on 
CJ2 CPU Unit 
(CJ2H-CPU
@@
-EIP/ 
CJ2M-CPU3
@
)
CJ-series 
PLC
Network device
Contents
(1) CS1W-EIP21 EtherNet/IP 
Units for CS-series PLCs, 
CJ1W-EIP21 EtherNet/IP 
Units for CJ-series PLCs, 
or built-in EtherNet/IP port 
in CJ2H-CPU
@@
-EIP/
CJ2M-CPU3
@
 CPU Units
These are Communications Units or built-in ports 
that connect a CS-series or CJ-series PLC to an Eth-
erNet/IP network.
(2) Twisted-pair cable
The twisted-pair cable connects EtherNet/IP Units or 
built-in EtherNet/IP ports to the switching hub, with 
an RJ45 Modular Connector at each end.
Use an STP (shielded twisted-pair) cable of category 
5, 5c, or higher.
(3) Switching Hub
This is a relay device that connects multiple nodes in 
a star-shaped LAN.