Omron CJ1W-EIP21 用户手册

下载
页码 464
6
Communications Services Overview
Section 1-4
Refer to the CX-Integrator Operation Manual (Cat. No. W464) for information
on the CX-Integrator. 
1-4
Communications Services Overview
The following communications services are supported.
CIP (Common Industrial Protocol) Communications Services
1) Tag Data Links (Cyclic Communications)
A program is not required to perform cyclic data exchanges with other devices
in the EtherNet/IP network.
Normally, the tag data links in an EtherNet/IP Unit or built-in EtherNet/IP port
are started by grouping the tags created with the Network Configurator into a
tag set, and establishing a connection with the target device using that group
of tags. One connection is used per group (tag set). Up to 32 connections for
the CJ2M and up to 256 connections for other CPU Units) can be registered.
The following table gives the tag and tag set specifications.
Personal computer 
running Windows 
CX-Integrator
Routing table 
settings
EtherNet/IP Unit or 
built-in EtherNet/IP port 
CS/CJ-series CPU Unit
Routing Table Area
Tags
Tag sets
CS1W-EIP21
CJ1W-EIP21
CJ2H-CPU
@@
-EIP
CJ2M-CPU3
@
CS1W-EIP21
CJ1W-EIP21
CJ2H-CPU
@@
-EIP
CJ2M-CPU3
@
Total size of all tags 
≤ 
184,832 words
Total size of all tags 
≤ 
640 
words
Maximum size of 1 tag set 
≤ 
722 words
(The maximum size is 721 
words when the tag set 
includes the PLC status.)
Maximum size of 1 tag set 
≤ 
20 words
(The maximum size is 19 
words when the tag set 
includes the PLC status.)
Maximum size of 1 tag 
≤ 
722 
words
(The maximum size is 721 
words when the tag set 
includes the PLC status.)
Maximum size of 1 tag 
≤ 
20 
words
(The maximum size is 19 
words when the tag set 
includes the PLC status.)
Number of tags per tag set 
≤ 
8
(7 tags/tag set when the tag set includes the PLC status)
Note Input and output variables cannot be combined.
Number of registrable tags 
≤ 
256
Number of registrable tags 
≤ 
32
Number of registrable tag 
sets 
≤ 
256
Number of registrable tag 
sets 
≤ 
32