Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports
Section 10-4
10-4 Tag Data Link Performance for CJ2M Built-in EtherNet/IP 
Ports
10-4-1 Overview
The built-in EtherNet/IP port on a CJ2M CPU Unit (CJ2M-CPU3
@
) supports
tag data links for up to 32 connections, with a data size of 20 words per con-
nection. These specifications are different from those of CJ2H built-in ports
and EtherNet/IP Units. The maximum number of words that can be transmit-
ted for tag data links is 640 words. This 640 words is the amount of data that
is processed for one data transmissions between the CPU Unit and the CJ2M
built-in port. 
The tag data link specifications of CJ2M built-in ports are provided in the fol-
lowing table. If these specifications are insufficient for the required system
configuration, use a CJ2H built-in port on a CJ2H-CPU6
@
-EIP CPU Unit or a
CJ1W-EIP21 EtherNet/IP Unit. 
Tag Data Link Specifications for CJ2M Built-in EtherNet/IP Ports
Tag Data Link System 
Configuration 
Example
This example configuration is based on the maximum specifications for CJ2M
built-in ports where all nodes send and receive data to the other nodes. In this
case, the maximum send area for each node in a 17-node configuration is 20
words. 
For example, node 1 establishes 16 send connections and 16 receive connec-
tions to the other 16 nodes, for a total of 32 connections. The maximum data
size per connection is 20 words, so the send area in node 1 is 20 words and
the receive areas in node 1 are each 20 words. 
CJ2M built-in port
(CJ2M-CPU3
@
)
Reference: CJ2H built-in port
(CJ2H-CPU6
@
-EIP)
Number of connections
32
256
Packet interval (RPI)
1 to 10,000 ms (in 0.5-ms units)
0.5 to 10,000 ms (in 0.5-ms units)
Allowed communications 
bandwidth per Unit (PPS)
3,000 pps
6,000 pps
Number of tags that can be 
registered
32
256
Tag types
CIO Area, DM Area, EM Area, Holding Area, Work Area, and network symbols
Number of registrable tag sets 32
256
Number of tags per connec-
tion
8 (7 tags when the tag set contains the PLC status)
Maximum size of 1 tag set
20 words
(The PLC status uses 1 word when the tag 
set contains the PLC status.)
722 words
(The PLC status uses 1 word when the tag 
set contains the PLC status.)
Maximum data size per con-
nection
20 words
722 words
Maximum link data size per 
node
640 words
184,832 words
Maximum number of tags that 
can be refreshed per CPU Unit 
cycle
Output/Transmission 
(CPU 
 EtherNet/IP): 32
Input/Reception (EtherNet/IP 
 CPU): 32
Output/Transmission 
(CPU 
 EtherNet/IP): 256
Input/Reception (EtherNet/IP 
 CPU): 256
Data that can be refreshed per 
CPU Unit cycle
Output/Transmission (CPU 
 EtherNet/IP): 
640 words
Input/Reception (EtherNet/IP 
 CPU): 
640 words
Note The total for output/transmission and 
input/reception is 640 words. 
Output/Transmission (CPU 
 EtherNet/IP): 
6,432 words
Input/Reception (EtherNet/IP 
 CPU): 
6,432 words
Note The total for output/transmission and 