Omron CJ1W-EIP21 用户手册

下载
页码 464
371
Troubleshooting with FINS Response Codes
Section 14-6
14-5-5 Message Timeout Problems
14-6 Troubleshooting with FINS Response Codes
The cause of errors that occur when using the SEND(090), RECV(098), or
CMND(490) instructions can be identified from the response codes. (Refer to
the description of Communications Port Completion Codes in 8-6-4 Writing
Programs
 
for the storage locations of response codes generated by the
SEND(090), RECV(098), or CMND(490) instructions.)
This section describes the completion codes produced by EtherNet/IP Units.
For details on completion codes produced by CPU Units, other CPU Bus
Units, or computers equipped with FINS services, refer to the device’s opera-
tion manual.
The 6
th
, 7
th
, and 15
th
 bits of the response codes have specific functions. The
6
th
 bit will be ON when a non-fatal error has occurred in the PLC at the remote
node; the 7
th
 bit will be ON when a fatal error has occurred in the PLC at the
remote node; and the 15
th
 bit will be ON when a network relay error has
occurred. The following table explains the meaning of the completion codes.
Timeout errors 
occur frequently in 
message services 
(CIP UCMM, CIP 
Class 3, or FINS).
• When there is a high load in the tag data link, and the CPU 
Unit’s cycle time is relatively long or there are messages 
coming in from many nodes, the message service response 
time may be delayed and messages may be discarded occa-
sionally.
• In this case, the communications load must be reduced by 
increasing (slowing) the tag data link’s RPI, reducing the 
message load, or increasing the timeout value.
• The tag data link’s bandwidth usage can be checked on the 
Monitor Device Window’s Ethernet Information Tab Page. 
Refer to 14-1 Checking Status with the Network Configurator 
for details.
• The error log error codes that indicate discarded messages 
(insufficient memory) due to heavy communications loads 
are 0117, 0119, 0123, 0125, 03C2 (detail code 
@@
08, 
@@
09, or 
@@
0A), 03C3, and 03D2. Refer to 14-1 Checking 
Status with the Network Configurator for details on reading 
the error codes on the Error History Tab Page.
• For information on preventing high loads in FINS communi-
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
First byte
Second byte
Bit
PLC Fatal Error Flag
PLC Non-fatal Error Flag
Relay Error Flag
Main response code (RES)
Sub response code (SRES)
Main response 
code
Sub response code
Item to check
Likely cause
Corrective action
Value and 
meaning
Value and meaning
00
Normal 
completion
00
---
---
---
---