Omron CJ1W-EIP21 用户手册

下载
页码 464
372
Troubleshooting with FINS Response Codes
Section 14-6
01
Local node 
error
03
Local node send 
error
---
Lack of available space in 
internal buffers
The load (traffic) on the Ether-
net Unit is too heavy. Check 
your user applications.
05
Node address set-
ting error
Local IP 
address
The network cannot be 
used because the IP 
address setting is incor-
rect.
Correct the local IP address.
07
Local node busy 
(send failed)
System load
Lack of available space in 
internal buffers
The load (traffic) on the Ether-
net Unit is too heavy. Check 
your user applications.
02
Remote 
node error
01
Remote node not in 
network
IP address 
table and IP 
router table
IP address of remote 
node not set correctly.
Set IP address of remote 
node into IP address table 
and, if internetwork transmis-
sion is required, into the IP 
router table.
02
No Unit with speci-
fied unit address
Instruction’s 
control data
There is no Unit with the 
specified unit address.
Check the remote node's unit 
address.
05
Response timeout
Transfer condi-
tions
(Use FINS 
status read 
commands.)
Message packet was cor-
rupted by transmission 
error.
Increase the number of trans-
mit retry attempts.
Instruction’s 
control data
The response monitoring 
time is too short. 
Set a longer response moni-
toring time.
Read the error 
log.
The transmission frame 
may be corrupted or the 
internal reception buffer 
full.
Read out the error log and 
correct the system as 
required.
03
Unit error 
(Controller 
error)
01
Communications 
controller error
Affected con-
troller’s ERC 
indicator 
Error occurred in the 
communications control-
ler.
Take corrective action, refer-
ring to troubleshooting proce-
dures in this section.
02
PLC error
Affected 
node’s LED 
indicators
CPU Unit error occurred 
in the PLC at the remote 
node.
Clear the error in the CPU 
Unit. (Refer to the PLC's oper-
ation manuals.)
04
Unit number setting 
error
Unit number
The unit number setting 
is incorrect.
Confirm that the unit number 
set on the switch is within the 
specified range and that the 
same unit number is not used 
twice in the same network.
04
Service not 
supported
01
Unsupported com-
mand
Command 
code
The specified command 
code is not supported by 
the destination Unit.
Check the command code.
FINS header 
frame length
A short frame (4 bytes) is 
being used for the FINS 
header frame.
The EtherNet/IP Unit does not 
support short headers.
05
Routing 
error
01
Routing table setting 
error
Routing tables Remote node is not set in 
the routing tables.
Set the destination address in 
the routing tables.
02
Routing tables not 
registered
Routing tables Destination is unknown 
because there are no 
routing tables.
Set routing tables at the local 
node, remote node, and any 
relay nodes.
03
Routing table error
Routing tables Routing table error
Set the routing tables cor-
rectly.
04
Too many relay 
points
Network con-
figuration
The maximum number of 
network levels (3) was 
exceeded in the com-
mand.
Redesign the network, or 
reconsider the routing tables 
to reduce the number of relay 
nodes in the command.
Main response 
code
Sub response code
Item to check
Likely cause
Corrective action
Value and 
meaning
Value and meaning