[c]FP-DO-403
mount the flyback diode within 18 in. of the load. Figure 5 shows 
a flyback diode connected to an inductive load.
Figure 5.  Connection to Inductive Load with Flyback Diode
Although the [c]FP-DO-403 contains flyback diodes to prevent 
excessively high voltage from damaging the module, National 
Instruments recommends the use of an external protection circuit 
across any inductive load.
Status Indicators
The [c]FP-DO-403 has two green status LEDs, POWER and 
READY. After you insert the FP-DO-403 into a terminal base 
or the cFP-DO-403 into a backplane and apply power to the 
connected network module, the green POWER indicator lights 
and the [c]FP-DO-403 informs the network module of its presence. 
When the network module recognizes the [c]FP-DO-403, it sends 
initial configuration information to the [c]FP-DO-403. After the 
module receives this initial information, the green READY 
indicator lights and the [c]FP-DO-403 is in normal operating 
mode.
In addition to the green POWER and READY indicators, each 
channel has a numbered, green output state indicator, which lights 
when the channel is in the ON state.
Isolation and Safety Guidelines
Caution
Read the following information before 
attempting to connect the [c]FP-DO-403 to any circuits 
that may contain hazardous voltages.
This section describes the isolation of the [c]FP-DO-403 and its 
compliance with international safety standards. The field wiring 
connections are isolated from the backplane and the inter-module 
communication bus. The isolation barriers in the module provide 
Flyback Diode 
V
OUT
Load 
V or V
SUP