National Instruments cFP-RTD-124 用户手册

下载
页码 15
© National Instruments Corp.
3
FP-RTD-124 and cFP-RTD-124
To install the cFP-RTD-124, refer to Figure 2 and complete the 
following steps:
1. Align the captive screws on the cFP-RTD-124 with the holes 
on the backplane. The alignment keys on the cFP-RTD-124 
prevent backward insertion. 
2. Press firmly to seat the cFP-RTD-124 on the backplane.
3. Using a number 2 Phillips screwdriver with a shank of at least 
64 mm (2.5 in.) length, tighten the captive screws to 1.1 N
⋅ m 
(10 lb
⋅ in.) of torque. The nylon coating on the screws 
prevents them from loosening.
Figure 2.  Installing the cFP-RTD-124
1
cFP Backplane
2
cFP Controller Module
3
cFP I/O Module
4
Captive  Screws
5
Screw Holes
4
4
3
2
1
5
5