Chapter 2
BridgeVIEW Environment
© National Instruments Corporation
2-13
Table 2-2 provides a description of each of the fields in the Engine 
Manager dialog box. This table provides basic information about the 
Engine Manager dialog box options. For a more complete understanding 
of how or why you might use the Engine Manager in a BridgeVIEW 
application, you must understand how to configure tags. See Chapter 3,
.
Table 2-2.  Engine Manager Field Descriptions
Field
Description
Engine Status
Displays the current status of the BridgeVIEW Engine—whether launching, 
running, or stopped. 
Log Historical 
Data
Turns on or off logging of historical data to file. This button is pressed 
automatically if you selected Start logging on system start-up in your 
configuration file. If you do not have a valid event log path configured, 
or do not have a printer configured, this checkbox is disabled. 
Log Events
Turns on or off logging of alarms and events to file. This button is pressed 
automatically if you selected Start event logging on system start-up in your 
configuration file. If you do not have a valid event log path configured, this 
checkbox is disabled.
Print Events
Turns on or off printing of alarms and events to your line printer. This button 
is pressed automatically if you selected Start printing on system start-up in 
your configuration file. If you do not have a printer configured, this checkbox 
is disabled.
Run/Stop Engine
Starts the BridgeVIEW Engine, or stops the BridgeVIEW Engine and shuts 
down any loaded servers. 
Quit Engine
Closes and exits the BridgeVIEW Engine process. 
Enable Error 
Dialog
Enables or disables the showing of the Error dialog box. If this box is checked, 
a System Error Display dialog box pops up for you to acknowledge the event 
when a system error occurs. 
Server Browser
Launches the Server Browser Utility. With this utility, you can see the servers 
in your system, including OPC servers; view server information; and display 
the server front panel if the server is running (VI-based servers only).
Show/Hide 
System Event 
Display
Shows or hides the System Event Display.