Chapter 3
Tag Configuration
© National Instruments Corporation
3-9
For easy viewing and editing in the spreadsheet, press the 
Use Default Order button.
After you edit the file, save it as a 
.txt
 file. Then, from the Tag 
Configuration Editor, select File»Import… to import the information 
from the spreadsheet file. 
If you use spreadsheet files with the Tag Configuration Editor, it is 
important that you understand the following points:
If you do not choose all of the fields when exporting your data, you 
lose configuration information when you import it back to the Tag 
Configuration Editor. 
You might choose to export a subset of information, and then rely 
on tag default parameters when you import the data back in to the 
Configuration Editor. However, each row in the spreadsheet file must 
contain the tag name and data type fields, or the import mechanism 
cannot read it.
Some configuration parameters, such as Historical Logging 
Configuration and Event Configuration, are inherited from the 
currently open 
.scf
 file when you import spreadsheet data.
When importing, you can append the imported tags to the current 
.scf
file.
Note
If the tag name and data type fields are missing, the File»Import… option does 
not work on the spreadsheet file.