Chapter 3
Tag Configuration
© National Instruments Corporation
3-27
Analog Tags
You can define the raw range and engineering range for a tag to perform 
simple conversions between the two ranges. The raw range, defined by 
Raw Full Scale and Raw Zero Scale, refers to the values used by the 
device server. Engineering range, defined by Engineering Full Scale 
and Engineering Zero Scale, refers to the values used by the BridgeVIEW 
Engine and HMI. Pull down the Scaling ring and select Linear to enable 
a linear (mx + b) conversion between raw and engineering ranges. Select 
Square Root to enable a square root conversion between the raw and 
engineering ranges. Figure 3-8 shows the Scaling tab of the Analog Tag 
Configuration dialog box. 
Figure 3-8.  Analog Tag Scaling Dialog Box
The following examples describe linear and square root scaling. 
Example
—
Linear Scaling
A device server returns a simple voltage from 0 to 5 V. The voltage is 
related to a position sensor, and the real-world position is measured in 
centimeters, with 0 volts mapped to 50 cm and 5 V mapped to 100 cm.