Chapter 3
Tag Configuration
© National Instruments Corporation
3-41
8.
Modify the 
Mixer
Liquid
, and 
Powder
 tags, as specified in 
Table 3-11, to configure them for Historical Logging and Alarm 
Acknowledgement. To edit a tag configuration, double-click the tag in 
the Tag Configuration Editor listbox or press the Edit Tag… button.
You can select multiple tags by holding the <Shift> key while 
dragging or clicking the mouse. When you edit multiple tags, the Tag 
Configuration dialog box shows three buttons: Edit Next TagOK
and Cancel. Select the Edit Next Tag to record any edits from the 
Tag Configuration dialog box and then display the next tag selected. 
Select OK to record any edits from the Tag Configuration dialog 
and return to the Tag Configuration Editor. Select Cancel to discard 
changes to the current tag and return to the Tag Configuration Editor.
Alarms
Enable Alarms
Enabled
Alarm Acknowledge 
Mode
Auto Ack on Normal
Alarm Deadband 
(% of range)
1.00
HI_HI 
Enabled, 
Limit = 
950.00, Priority = 1
HI 
Enabled, 
Limit = 
800.00, Priority = 1
LO
Disabled
LO_LO
Disabled
Bad Status Alarm
Enabled, 
Priority = 1
Table 3-11.  Configuration Modifications for Activity 3-1
Category
Attribute
Setting
Operations
Log Data
Enabled
Log Deadband 
(% of range)
0.00
Log Resolution
0.10
Table 3-10.  Configuration Settings for Activity 3-1 (Continued)
Category
Attribute
Setting