GE EX2100 用户手册
B-2
••••
Appendix B Ratings and Specifications
GEH-6632 EX2100 User’s Guide
Input/Output
QTY
Potential transformers (PTs)
2
3-phase standard, single-phase available
120 V ac nominal
1 VA nominal burden
1 VA nominal burden
Current transformers (CTs, 1 or 5 A)
2
Any two phases, single phase is available
1 VA nominal burden
86G dedicated contact input
1
Open for trip
52G dedicated contact input
1
Closed for online
Trip rated contact outputs
2
At 125 V dc the relay break characteristics are:
Resistive load 0.5 A
Inductive load 0.2 A
Inductive load 0.2 A
General Purpose contact inputs
6
Customer contact, 70 V dc supplied by ECTB
General Purpose Form C contact outputs
4
At 125 V dc the relay break characteristics are:
Resistive load 0.5 A
Inductive load 0.1 A
Inductive load 0.1 A
± 10 V differential amplifier input
1
Control
Automatic ac Voltage Regulation
Automatic ac Voltage Regulation
Proportional + Integral, software implemented
± 0.25 % over full voltage range
± 0.25 % over full voltage range
Manual dc Voltage regulator
Proportional + Integral, software implemented
± 2.0 % over full voltage range
± 2.0 % over full voltage range
Protection Features
Under Excitation Limiter, (UEL)
Over Excitation protection (76)
Generator Field Ground detection (64F)
Generator Overvoltage protection (24G)
Loss of Excitation protection (40)
V/Hz limit (24) and trip (24T)
Bridge Over Temperature (26)
Field Over Temperature (49)
Phase Unbalance (22)
PT Failure (60)
Over Excitation protection (76)
Generator Field Ground detection (64F)
Generator Overvoltage protection (24G)
Loss of Excitation protection (40)
V/Hz limit (24) and trip (24T)
Bridge Over Temperature (26)
Field Over Temperature (49)
Phase Unbalance (22)
PT Failure (60)
Environmental Control & Protection
Base controls cabinet
Base controls cabinet
Continuous operation in a 0 to 40 ºC ambient environment
Base power bridge and auxiliary cabinet
Continuous operation in a 0 to 40 ºC ambient environment, with 5 to 95%
humidity, non-condensing
humidity, non-condensing
Storage Temperature
-40 ºC to +70 ºC
Humidity
5 to 95% humidity, non-condensing
Altitude
Normal operation at 0 to 1000 m. Derate 6% per 1000 m above 1000 m
Cooling
Forced air cooling required for PCM cabinet
Contaminants, withstand 10 PPB of
these:
these:
Reactive Sulfur, Reactive Chlorine, Hydrogen Sulfide
Sulfur Dioxide, Chlorine Dioxide, Sulfuric Acid
Hydrochloric Acid, Hydrogen Chloride, Ammonia
Sulfur Dioxide, Chlorine Dioxide, Sulfuric Acid
Hydrochloric Acid, Hydrogen Chloride, Ammonia
Vibration
Seismic
Seismic
Universal Building Code (UBC) – Seismic Code section 2312 Zone 4
Shipping
72 hours at 0.3 G rms between 4 to 16 Hz
3 shocks of 15 G, 2 ms impulse for all three axes
3 shocks of 15 G, 2 ms impulse for all three axes
Operating/Installed at Site
1.0 G Horizontal, 0.5 G vertical at 15 to 150 Hz