- 45 - 
5.1.1. 
Instance 20: CIP basic speed control output 
 
Instance 20 mapping 
Byte 
Bit 7 
Bit 6 
Bit 5 
Bit 4 Bit 
3 Bit 
2 Bit 
1 Bit 
- - - - - 
Fault 
reset
Run 
Fwd 
1 - 
Drive Speed Reference 
min
-1
 (Low byte) * 
Drive Speed Reference 
min
-1
 (High byte) * 
 
 
5.1.2. 
Instance 70: CIP basic speed control input 
 
Instance 70 mapping 
Byte 
Bit 7 
Bit 6 
Bit 5 
Bit 4 Bit 
3 Bit 
2 Bit 
1 Bit 
- - - - - 
Running1* 
(Fwd) 
- Faulted 
1 - 
Drive Actual Speed 
min
-1
 (Low byte) 
Drive Actual Speed 
min
-1
 (High byte) 
* Running1 means "Running Forward." 
 
Examples of Instance 20/70 
 
(1) Stop 
Instance 
Byte  15 14 13 12 11 10 9
8
7
6
5
4
3  2  1  0 
Hex. 
1,  0 
0
0
0
0 0 0 0 0
0
0
0x0000 
Output Instance 20 
3,  2   
-
-
-
-
-
-
-
-
-
-
1,  0 
0
0
0
0 0 0 0 0
0
0
0x0000 
Input Instance 70 
3,  2   
0
0
0
0 0 0 0 0
0
0
0x0000 
 
 
 
 
 
 
 
 
 
 
 
 
 
(2) Forward running 1800 rpm ** 
Instance 
Byte  15 14 13 12 11 10 9
8
7
6
5
4
3  2  1  0 
Hex. 
1,  0 
0
0
0
0 0 0 0 0
0
0
0x0001 
Output Instance 20 
3, 
  0 0 0
0
0
1
1
1
0 0
0
0
0 0 0  0x0708 
1,  0 
0
0
0
0 0 0 0 0
0
0
0 0  0x0004 
Input Instance 70 
3, 
  0 0 0
0
0
1
1
1
0 0
0
0
0 0 0  0x0708 
 
 
 
 
 
 
 
 
 
 
 
 
 
(3) Fault reset *** 
Instance 
Byte  15 14 13 12 11 10 9
8
7
6
5
4
3  2  1  0 
Hex. 
1,  0 
0
0
0
0 0 0 0 0
0
0
0 0  0x0004 
Output Instance 20 
3,  2   
-
-
-
-
-
-
-
-
-
-
 
** 
Drive Reference Speed
 is set up number of rotations by the hexadecimal number. 
For example, when "Frequency reference" is set up to 1800 min
-1
1800 = 708H 
 
*** Fault reset works only 1 time when 0 -> 1.