RuggedCom RS969 用户手册

下载
页码 31
19 
 
2008 RuggedCom Inc. All rights reserved 
 
Rev104
 
 
2.7  Fast Ethernet Ports – Signal Description 
 
The RS969 series switches have several 10/100BaseTX ports that allow connection to standard 
CAT-5 UTP cable with industrial RJ45 male connectors or industrial D-coded M12 male 
connectors. The RJ45/M12 receptacles are directly connected to the chassis ground on the M969 
and can accept shielded CAT-5 cables. If shielded cables are used, care must be taken to ensure 
the shielded cables do not form a ground loop via the shield wire and the RJ45/M12 receptacles at 
either end. Figure 2.6.1 shows the pin configuration.  
 
Pin
Signal
1
+Rx
2
-Rx
3
+Tx
4
No Connection
5
No Connection
6
-Tx
7
No Connection
8
No Connection
Case Shield (Chassis Ground)  
 
Figure 2.6.1 RJ45 Port  and M12 Port Pins 
 
NOTE: RuggedCom does not recommend the use of CAT-5 cabling of any length for critical real-
time substation automation applications. However, transient suppression circuitry is present on all 
copper ports to protect against damage from electrical transients and to ensure IEC 61850-3 and 
IEEE 1613 Class 1 conformance. This means that during the transient event communications 
errors or interruptions may occur but recovery is automatic. 
 
RuggedCom also does not recommended to use these ports to interface to field devices across 
distances which could produce high levels of ground potential rise, (i.e. greater than 2500V) during 
line to ground fault conditions.