RuggedCom RS969 用户手册

下载
页码 31
20 
 
2008 RuggedCom Inc. All rights reserved 
 
Rev104
 
3  Technical Specifications 
 
3.1  Operating Environment 
 
Parameter 
Range 
Comments 
Ambient Operating Temperature 
-40 to 85
°C 
Ambient Temperature as 
measured from a 30 cm radius 
surrounding the center of the 
M969 enclosure. 
Ambient Relative Humidity 
5% to 95% 
Non-condensing 
Ambient Storage Temperature 
-40 to 85
°C 
 
IP Rating 
IP67 
 
Operating Altitude 
0 to 15240m (0 to 50000 ft) 
Over temperature range of -40 
to 85
°C 
 
3.2  Power Supply Specifications 
 
Power Supply Type 
Minimum 
Input 
Maximum 
Input 
Fuse 
Rating 
Isolation 
Maximum Power 
Consumption 
12 – 24 VDC 
10 VDC 
36 VDC 
3.15A (T) 
1.5 kV DC 
24 VDC 
18 VDC 
36 VDC 
3.15A (T) 
1.5 kV DC 
48 VDC 
36 VDC 
72VDC 
3.15A (T) 
1.5 kV DC 
HI (125/250 VDC) 
1
 
HI (110/230 VAC) 
1
 
88 VDC 
85 VAC 
300 VDC  
265 VAC 
3.15A (T) 
4 kV AC  5.5 
kV DC 
10W 
 
NOTES: 
1.
  This is the same power supply for both AC and DC. 
2.
  (T) denotes time-delay fuse 
3.
  For continued protection against risk of fire, replace only with same type and rating of fuse. 
 
3.3  Failsafe Relay Specifications 
 
Parameter 
Value 
Max Switching Voltage 
30VAC, 80VDC 
Rated Switching Current 
0.3A @ 30VAC 
1A @ 30VDC, 0.3A @ 80VDC 
 
NOTES: 
1.
  Resistive Load. 
2.
  For Class-2 circuits only.