Serial Protocols 
 
 
ROS™  v3.5 
84 
RS400 
 
Figure 54: Device Address Form 
 
Protocol 
Synopsis: { ModbusServer, ModbusClient, DNP, WIN, TIN, MicroLok } 
Default: ModbusServer 
The serial protocol supported on this serial port. 
Address 
Synopsis: Any 31 characters 
Default:  
The destination (source) device address. Could be local or remote. Local address is the address 
of the device connected to the serial port on this device, and serial port must be configured. 
Remote address is the address of the device connected to the remote host's serial port. In that 
case RemoteIpAddr must be configured. NOTE: The range and format of the address is defined 
by protocol: 
Modbus: 1 to 244 
MicroLok: 1 to 65535, or 8 to  hexadecimal digits  ‘1’ to ‘a’ 
DNP 3.0: 1 to 65520 
WIN: 6 bits address (0 to 63) 
TIN: String 'wdr' for wayside data radio (TIN mode 2), or 32 bits address, 8 digits, allowed are 
hexadecimal digits '0' to 'f'. All zeros are not allowed. 
Remote IP Addr 
Synopsis: ###.###.###.###  where ### ranges from 0 to 255 
Default:  
The IP address of remote host where device with configured remote address is connected. 
Port 
Synopsis: 1 to maximum port number or {Unknown}