Liebert AC4 用户手册

下载
页码 88
System and Control Options
26
7.0
S
YSTEM
 
AND
 C
ONTROL
 O
PTIONS
The System and Control menu allows you to configure the AC4—setting up inputs and outputs and 
system features such as date and time. This menu also provides a vehicle for manually changing the 
state of an output to ON or OFF, clearing active alarms and deleting records from the AC4’s alarm 
and event logs.
The arrows
↑↓
 are used to scroll through the menu. The Enter
↵ 
key is used to select the menu item 
and enter new information. Table 12 shows characters that may be entered in labels and values.
The System and Control options require a password to prevent unauthorized users from making 
changes to the system.
This section presents step-by-step instructions for each of the following:
• Login - enter the password
• Setup System - configure inputs, outputs, system features
• Override Output - manually override automatic control of outputs; release the override
• Clear Alarms & Logs - clear active alarms; delete records from the alarm and event logs
7.1
Login
Users must enter a password to access any of the system and control 
options. The password consists of four characters (see Table 12 for 
valid characters). (To set up or change the password, see 7.7.1 - 
Change Password.) The default password is AAAA.
To log in:
• From the Main Menu, use the arrows
↑↓
 to
 
choose System and 
Control, then press Enter
, as shown at right.
• Use the arrows
↑↓
 to
 
choose System and Control, and press 
Enter
. The Login menu appears.
• To enter your password:
• Use the arrows
↑↓
 to
 
choose a character.
• Press Enter
↵ 
to advance to the next character position.
• When finished, press Enter
 again.
The System and Control Menu appears next, with these options that 
are described in the following sections:
• Setup System (Section 7.2 - Section 7.7)
• Override Output (Section 7.9)
• Clear  Alarms  &  Logs  (Section 7.10)
NOTE
For ease of understanding, this section uses the LCD interface to illustrate most instructions, 
except for features that are available only through the Service Terminal Interface. All Service 
Terminal Interface screens appear in Appendix A - Service Terminal Interface
Table 12
Valid characters for data entry
Alphanumeric
Special characters
A-Z, 0-9
space [ ] ^ _ ! " # $ % & ( ) * + - / , . ; < = > @
NOTE
If an alarm occurs while a user is logged on, the LCD backlight will flash and the audible 
alarm will sound. To obtain specific information about the alarm, you must access the Active 
NOTE
If, after logging in, you press the ESC key to return to a previous screen that is not password-
protected, you must log in again, including entering your password if you wish to access 
password-protected functions.
Main Menu
VIEW STATUS
> SYSTEM AND CONTROL
↑↓
=NEXT
=SELECT
Login
LOGIN
AAAA
↑↓
=SELECT
=NEXT/END
System & Control Menu
> SETUP SYSTEM
OVERRIDE OUTPUT
CLEAR ALARMS & LOGS
↑↓
=NEXT
=SELECT