System and Control Options
28
7.2
Setup System - Overview
The Setup System screen displays six options that allow you to configure input and output devices, 
the common alarm, and a variety of system details, such as login password and system date and time:
• Setup Inputs
• Setup Common Alarm
• Setup Zones
• Setup Outputs
• Setup System Info
• Setup Operation
7.3
Setup System - Setup Inputs
The AC4 has four digital input points that may be configured individ-
ually. These inputs may have a wide variety of Liebert or other manu-
facturers’ equipment connected.
To configure a digital input:
Log In and Choose Setup System
• From the Main Menu, use the arrows
↑↓
 to
 
choose System and 
Control, then press Enter
 (see 7.1 - Login for help)
.
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
↑↓
 to
 
choose 
Setup System, then press Enter
.
Select a Digital Input to Configure
• From the Setup System Menu, shown at right, use the arrows
↑↓
 to
 
choose Setup Inputs and 
press Enter
.
• From the Select Input Menu, choose an input—for example, Device_1—and press Enter
.
Table 13 shows the digital input features you may change, along with the default settings: you may 
change the name of the input, define it as normally open or closed, and specify it as alarmable or as an 
event.
• Alarmable inputs may be defined as either Unlatched or Latched.
• Event status allows you to monitor a digital input’s state—and use a change in state to initiate an 
action through an output, if desired—without triggering an alarm. Events are always Unlatched.
• You may also specify a time delay before the AC4 responds to an alarm or event.
Use the steps following Table 13 to change the default settings for any digital input.
Table 13
Default settings - digital inputs
Feature
Default
Other Options
LABEL
DEVICE_1
Any name (up to eight characters)
NORM OPEN/CLOSE
NO (Normally open)
NC (Normally closed)
ALARM/EVENT
AL (Alarmable)
EV (Event)
LATCHED
L (Latched) / Y (Yes)*
NL (Unlatched) / N (No)*
DELAY
00:01 (1 second)
Any time (in minutes and seconds) from 00:00 to 99:59
NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.
Settings - Select Input Menu
(see Section 7.3)
When configuring an input
(see Section 7.3.4)
Unlatched
NL (Not Latched)
N (No, not latched)
Latched
L (Latched)
Y (Yes, latched)
Setup System Menu
> SETUP INPUTS
SETUP COMMON ALARM
SETUP ZONES
↑↓
=NEXT
=SELECT
SETUP OUTPUTS
SETUP SYSTEM INFO
SETUP OPERATION
Select Input Menu
SELECT INPUT
> DEVICE_1  NO-AL-NL
DEVICE_2  NO-AL-NL
↑↓
=NEXT
=SELECT
DEVICE_3  NO-AL-NL
DEVICE_4  NO-AL-NL