Liebert AC4 用户手册

下载
页码 88
System and Control Options
30
7.3.4 Set Up Alarmable Inputs in Latched or Unlatched Mode
Alarmable input points may be set up in Latched mode (Y), which 
requires the user to clear the AC4 alarms after an alarm has occurred, 
or Unlatched mode (N), in which alarms will automatically clear after 
a return-to-normal state. The default setting for alarmable inputs is 
Y (Latched). Any input defined as an event is automatically 
Unlatched.
An input defined as Latched does not reset automatically after an 
alarm. It will remain in the triggered position even after the moni-
tored device returns to normal. After an alarm, the user must manu-
ally reset Latched inputs, as described in 7.10.1 - Clear Active 
Alarms. This also means that any outputs linked to a Latched digital 
input will remain triggered until the input is manually reset.
An input defined as Unlatched will automatically track the status of 
the monitored device. No action by the user is required.
• From the Setup Inputs Menu, choose Latched, as shown above 
right, and press Enter
.
• To change this feature, use the arrows
↑↓
 to
 
choose Y (Yes - 
Latched) or N (No - Unlatched), then press Enter
.
NOTE: Only alarmable input points may be set up as Latched. If you 
attempt to set up an event as Latched, the message shown at right 
appears. Press the ESC key to return to the previous screen to con-
tinue configuring the digital input.
The only way to reset latched alarms is by clearing active alarms. This 
step is required to return latched points to their normal state. For 
7.3.5 Set Up Delay Time
Each input may be set up with a specified time delay between the 
occurrence of an alarm or event—a monitored device changes state—
and any response by the AC4. This feature can prevent needless 
responses to transient conditions.
This delay is the amount of time that must elapse before the AC4 
acknowledges the change of state in the monitored device and takes 
any further action, such as dialing configured pagers. The default time 
delay is 1 second (displayed as 00 MIN : 01 SEC).
The time delay applies only when a monitored device changes from its 
normal state—for example, the AC4 detects a closed contact that is 
defined as Normally Open.
When the monitored device returns to its normal state, the AC4 
acknowledges the change of state after the delay timer ends its 
countdown.
• From the Setup Inputs Menu, choose Delay, as shown at right, and press Enter
.
• To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):
• For minutes (MIN), press and hold one of the arrow keys
↑↓
 scroll through the numbers 00-99.
• Press Enter
↵ 
to advance to seconds (SEC).
• For seconds (SEC), press and hold one of the arrow keys
↑↓
 scroll through the numbers 00-59.
• When finished, press Enter
 again.
Setup Inputs Menu
SETUP DEVICE_1
LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
↑↓
=NEXT
=SELECT
> LATCHED: N
DELAY: 00:01
Latched / Unlatched
IS ALARM
LATCHED? N
↑↓
=Y/N
=END
Message (if input has 
been defined as an event)
LATCH NOT ALLOWED
WHEN IN EVENT MODE
ESC=BACK
Setup Inputs Menu
SETUP DEVICE_1
LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
↑↓
=NEXT
=SELECT
LATCHED: N
DELAY: 00:01
Delay Time
DELAY TIME BEFORE
TRIGGER?
00 MIN : 01 SEC
↑↓
=SELECT 
=NEXT/END