FieldServer FS-8700-31 用户手册

下载
页码 26
FS-8700-31 
Siemens 
TIWAY 
           Page 
12 
of 
23 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com
 
2, 33 
49, 
0s 
 
The above map descriptor will continuously write data of type “Drum_Count_Preset” to 2 PLC data memory 
addresses. The data to write will be collected from the data array “RAW16_Data” from an offset of 70 and 71. The 
Preset Steps associated with the addresses are (address 5):33 and (address 9):49. 
 
4.4.6. 
TIWAY host adapter command map descriptor examples 
A number of map descriptors that send specific host adapter commands are available mainly for testing purposes 
and should not be used under normal circumstances. 
 
4.4.6.1. 
Read Secondary Log 
Returns a list of secondary PLC stations addresses that are connected. 
 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Host_Adapter_Cmd, Length, 
C37_READ_SEC_LOG, Secondary_Log, 
0, 
RDBC, 
PLC_01, 
Read_Secondary_Log, 
254, 
 
Scan_Interval 
0s 
 
The above map descriptor will continuously execute the indicated host adapter command and will store the list of 
connected secondary PLCs in the data array “Secondary Log” from an offset of 0. Offset 0 will correspond to 
secondary address 1, offset 1 to secondary 2 up to offset 253 corresponding to secondary address 254. 
 
 
4.4.6.2. Report 
HIU Configuration 
Reports the HIU Configuration option values that was used to configure the HIU. 
 
Map_Descriptor_Name, Data_Array_Name, 
Data_Array_Offset, Function, Node_name, TIWAY_Host_Adapter_Cmd, Length, 
C38_REP_HIU_CONFIG, HIU_Config, 
0, 
RDBC,  PLC_01, 
Report_HIU_Config, 
5, 
 
Scan_Interval 
0s