FieldServer FS-8700-31 用户手册

下载
页码 26
FS-8700-31 
Siemens 
TIWAY 
           Page 
14 
of 
23 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com
 
C40_REP_NM_CONFIG, Nm_Config, 
0, 
RDBC, PLC_01,  Report_NM_Config, 
16, 
 
Scan_Interval 
0s 
 
The above map descriptor will continuously execute the indicated host adapter command and will store the 
following parameter values in the data array “Nm_Config”: 
 
Offset Parameter 
Dipswitch 1 and 2 settings 
Config flag ( 0 = Network Manager not configured, 1 = Network Manager configured ) 
Option 01 configuration value 
Option 02 configuration value 
Option 03 configuration value 
Option 04 configuration value 
Option 05 configuration value 
Option 06 configuration value 
Option 07 configuration value 
Option 08 configuration value 
10 
Option 09 configuration value 
11 
Option 0A configuration value 
12 
Option 0B configuration value 
13 
Option 0C configuration value 
14 
Option 0D configuration value 
15 
Option 0E configuration value 
 
 
 
 
4.4.6.5. Soft 
Reset 
Forces the UNILINK Host Adapter to do a software reset. 
 
Map_Descriptor_Name, Data_Array_Name, 
Data_Array_Offset, Function, Node_name, TIWAY_Host_Adapter_Cmd, Length 
C41_SOFT_RESET, Cmd_Triggers, 
0, AWT, 
PLC_01, 
Soft_Reset, 1 
 
The above map descriptor will execute the indicated host adapter command once every time a value is written to 
the data array “Cmd_Triggers” at offset 0.