FieldServer FS-8700-128 用户手册

下载
页码 15
FS-8700-128 Safetran SCS-128 Manual 
 
 
 
 
 
Page 11 of 15 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.FieldServer.com 
Tel: 408 262-2299   Fax: 408-262-2269   Toll_Free: 888-509-1970   email: support@FieldServer.com 
5. 
Configuring the FieldServer as a Safetran-SCS-128 Server 
For  a  detailed  discussion  on  FieldServer  configuration,  please  refer  to  the  FieldServer 
Configuration Manual.  The information that follows describes how to expand upon the factory 
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files 
provided with the FieldServer). 
This section documents and describes the parameters necessary for configuring the FieldServer 
to communicate with a Safetran-SCS-128 Client.  When configured as a Server, the FieldServer 
is unable to keep synchronism with other Servers and Clients on the network if it is being polled 
using ‘Poll’ Function (i.e. single byte message).  Therefore the FieldServer must be polled with 
‘Recall’  request  for  indication  statuses.    The  FieldServer  will  always  respond  with  the  current 
statuses. 
The configuration file tells the FieldServer about its interfaces, and the routing of data required. 
In  order  to  enable  the  FieldServer  for  Safetran-SCS-128  communications,  the  driver 
independent  FieldServer  buffers  need  to  be  declared  in  the  “Data  Arrays”  section,  the 
FieldServer  virtual  Node(s)  needs  to  be  declared  in  the  “Server  Side  Nodes”  section,  and  the 
data  to  be  provided  to  the  clients  needs  to  be  mapped  in  the  “Server  Side  Map  Descriptors” 
section.  Details on how to do this can be found below. 
 
Note  that  in  the  tables,  *  indicates  an  optional  parameter,  with  the  bold  legal  value  being  the 
default. 
5.1. 
Server Side Connection Descriptors 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify which port the device is connected to the 
FieldServer 
P1-P8
2
 
Protocol 
Specify protocol used 
SCS-128 
SCS128 
Safetran SCS-128 
Baud* 
Specify baud rate 
75,  150,  300  ,600, 
1200, 
2400, 
9600 
(Vendor limitation) 
Parity* 
Specify parity 
Even 
(Vendor 
limitation) 
Data_Bits* 
Specify data bits 
8 (Vendor limitation) 
Stop_Bits* 
Specify stop bits 
1 (Vendor limitation) 
Handshaking* 
Specify hardware handshaking 
None 
Server_Hold_Timeout 
Specifies  time  FieldServer  will  reserve  Server 
side connection while waiting for the Client side to 
update data in Data_Array (if necessary)  
>1.0s 
 
                                                 
2
 
Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 
manual for details of the ports available on specific hardware.