Chapter 2
Function Reference — Config_Alarm_Deadband
©
 National Instruments Corporation
2-65
NI-DAQ FRM for PC Compatibles
alarmOnMessage and alarmOffMessage are messages you define. When the alarm-on 
condition occurs, NI-DAQ passes alarmOnMessage back to you. Similarly, when the 
alarm-off condition occurs, NI-DAQ passes alarmOffMessage back to you. The messages 
can be any value.
In Windows, you can set the message to a value including any Windows predefined messages 
such as 
WM_PAINT
. However, to define your own message, you can use any value ranging 
from 
WM_USER 
(0x400) to 0x7fff. This range is reserved by Microsoft for messages you 
define.
callbackAddr is the address of the user callback function. NI-DAQ calls this function when 
DAQEvent
 occurs. See 
Config_DAQ_Event_Message
 for restrictions on this parameter.
Using This Function
To meet the high alarm-on condition, the input signal must first go below 
(trigLevel deadbandWidth/2) volts and then go above (trigLevel deadbandWidth/2) 
volts. On the other hand, to meet the high alarm-off condition, the input signal must first go 
above (trigLevel + deadbandWidth/2) volts and then go below 
(trigLevel – deadbandWidth/2) volts. See Figure 2-1 for an illustration of the high alarm 
condition.
Figure 2-1.  High Alarm Deadband
The low alarm deadband trigger condition is the opposite of the high alarm deadband 
trigger condition. To meet the low alarm-on condition, the input signal must first go above 
(trigLevel deadbandWidth/2) and then go below (trigLevel deadbandWidth/2). On 
the other hand, to meet the low alarm-off condition, the input signal must first go below 
(trigLevel – deadbandWidth/2) and then go above (trigLevel + deadbandWidth/2). 
See Figure 2-2 for an illustration of the low alarm condition.
on
off
trigLevel +
deadbandWidth/2
trigLevel -
deadbandWidth/2
trigLevel
On:  high alarm on
Off:  high alarm off
Time