Chapter 2
Function Reference — Config_Alarm_Deadband
NI-DAQ FRM for PC Compatibles
2-66
©
 National Instruments Corporation
Figure 2-2.  Low Alarm Deadband
Config_Alarm_Deadband
 is a high-level function for NI-DAQ event messaging. Because 
this function uses the current inputRange and polarity settings to translate triglevel and 
deadbandWidth from volts to binary, you should not call 
AI_Configure
 and change these 
settings after you have called 
Config_Alarm_Deadband
. For more information on NI-DAQ 
event messaging, see the low-level function 
Config_DAQ_Event_Message
. When you are 
using this function, the analog input data acquisition must be run with interrupts only 
(programmed I/O mode). You cannot use DMA. See 
Set_DAQ_Device_Info
 for how to 
change modes.
trigLevel +
deadbandWidth/2
trigLevel -
deadbandWidth/2
trigLevel
On:  low alarm on
Off:  low alarm off
on
off
Time