Schneider Electric VW3 A3 303 用户手册

下载
页码 47
19
6. 4. Communication faults
A Modbus fault is triggered if the Modbus card does not receive any Modbus requests at its address within a predefined time period (time
out). All Modbus request types are taken into account (read, write, etc.). The time out is fixed at 10 s (non-modifiable).
The response of the drive in the event of a Modbus communication fault can be configured.
         
    
The values of the 
[Network fault mgt]
 
(
CLL)
 parameter, which trigger a 
[Com. network]
 
(
CnF)
 drive fault, are:
The values of the 
[Network fault mgt]
 
(
CLL)
 parameter, which do not trigger a drive fault, are:
The fallback speed can be configured via the 
[Fallback speed]
 
(
LFF)
 parameter in the 
[1.8 – FAULT MANAGEMENT]
 
(
FLt-)
 menu.
Configuration can be performed using the graphic display terminal or 
integrated display terminal using the 
[Network fault mgt]
 
(
CLL)
 
parameter in the 
[1.8 FAULT MANAGEMENT]
 
(
FLt-)
 menu, 
[COM. 
FAULT MANAGEMENT]
 
(
CLL-)
 submenu.
RDY
NET
+0.00Hz
0A
COM. FAULT MANAGEMENT           
Network fault mgt
:                Freewheel
CANopen fault mgt
:                Freewheel
Modbus fault mgt
:                Freewheel
                         
Code
Quick
Value
Meaning
[Freewheel]
 
(
YES)
Freewheel stop (factory setting)
[Ramp stop]
 
(
rMP)
Stop on ramp
[Fast stop]
 
(
FSt)
Fast stop
[DC injection]
 
(
dCI)
DC injection stop
Value
Meaning
[Ignore]
 
(
nO)
Fault ignored
[Per STT]
 
(
Stt)
Stop according to configuration of 
[Type of stop]
 
(
Stt)
.
[fallback spd]
 
(
LFF)
Switch to fallback speed, maintained as long as the fault is present and the run command is not disabled.
[Spd maint.]
 
(
rLS)
The drive maintains the speed at the time the fault occurred, as long as the fault persists and the run 
command has not been removed.