6. 5. Monitored parameters
It is possible to select up to 4 parameters to display their values in the 
[1.2 - MONITORING]
 menu (
[COMMUNICATION MAP]
 submenu)
on the graphic display terminal.
The selection is made via the 
[6 – MONITOR CONFIG.]
 menu (
[6.3 - CONFIG. COMM. MAP]
 submenu).
         
    
One of the three display formats below can be assigned to each monitored word:
Each parameter 
[Address 1 select] ... [Address 4 select]
 can be used to 
choose the logic address of the parameter. Select an address of zero 
to disable the function.
In the example given here, the monitored words are:
• Parameter 1 = Motor current (LCr): logic address 3204; 
signed decimal format
• Parameter 2 = Motor torque (Otr): logic address 3205; signed 
decimal format
• Parameter 3 = Last fault occurred (LFt): logic address 7121; 
hexadecimal format
• Disabled parameter: address 0; default format: hexadecimal format
RDY
NET
+0.00Hz
0A
6.3 CONFIG. COMM. MAP.           
Address 1 select
:                        3204
FORMAT 1
:                       Signed
Address 2 select
:                        3205
FORMAT 2
:                       Signed
Address 3 select
:                        7121
Code
Quick
FORMAT 3
:                        Hex
Address 4 select
:                              0
FORMAT 4
:                         Hex
Format
Range
Terminal display
Hexadecimal
0000 ... FFFF
[Hex]
Signed decimal
-32,767 ... 32,767
[Signed]
Unsigned decimal
0 ... 65,535
[Unsigned]