8. 9. Read/Write Multiple Registers (23 = 16#17)
Request:
Response:
Example: This example combines the two examples for functions 3 and 16. With function 23, the line is less busy than with these two
functions. However, the number of words that can be read and written is restricted.
• Write the values 20 (16#14) and 30 (16#1E) respectively to the 2 logic address words 9001 and 9002 on slave 2.
• Read the 4 logic address words 3102 to 3105 on the same slave (values read = 16#0028, 16#0258, 16#01F4, and 16#0000).
Request:
Response:
Slave no.
17
No. of 1
st
 word to be 
read
Number of words to be 
read
No. of 1
st
 word to be 
written
Number of words to be 
written
---
Hi
Lo
Hi
Lo
Hi
Lo
Hi
Lo
---
1 byte
1 byte
2 bytes
2 bytes
2 bytes
2 bytes
---
Number of bytes to be 
written
Value of 1
st
 word to be 
written
Value of last word to be written
CRC16
---
Hi
Lo
-----------------------------
Hi
Lo
Lo
Hi
1 byte
2 bytes
2 bytes
2 bytes
Slave no.
17
Number of bytes 
read
Value of 1
st
 word read
Value of last word read
CRC16
Hi
Lo
--------------
Hi
Lo
Lo
Hi
1 byte
1 byte
1 byte
2 bytes
2 bytes
2 bytes
Slave no.
Request code
No. of 1
st
 word to be 
read
No. of words to be 
read
No. of 1
st
 word to be 
written
No. of words to be 
written
---
Hi
Lo
Hi
Lo
Hi
Lo
Hi
Lo
---
02
17
0C
1E
00
04
23
29
00
02
---
---
No. of bytes to be written
Value of 1
st
 word to be written
Value of 2
nd
 word to be written
CRC
CRC
---
Hi
Lo
Hi
Lo
Lo
Hi
---
04
00
14
00
1E
D2
F5
Slave no.
Response code
No. of bytes 
read
Value of 1
st
 word read
Value of 2
nd
 word read
Value of 3
rd
 word read
Value of 4
th
 word read
CRC
CRC
Hi
Lo
Hi
Lo
Hi
Lo
Hi
Lo
Lo
Hi
02
17
08
00
28
02
58
01
F4
00
00
12
F0