8. 10. Read Device Identification (43 = 16#2B)
Request:
Response:
The total response size given in this example equals 55 bytes.
The response contains the following four objects:
Slave no.
2B
Type of MEI 
0E
ReadDeviceId 
01
Object Id 
00
CRC16
Lo
Hi
1 byte
1 byte
1 byte
1 byte
1 byte
2 bytes
Slave no.
2B
Type of MEI 
0E
ReadDeviceId 
01
Degree of conformity
02
-------
1 byte
1 byte
1 byte
1 byte
1 byte
-------
Number of additional frames
00
Next object Id 
00
Number of objects
04
-------
1 byte
1 byte
1 byte
-------
Id of object no. 1
00+
Length of object no. 1
0D
Value of object no. 1
“Telemecanique”
-------
1 byte
1 byte
13 bytes
-------
Id of object no. 2
01
Length of object no. 2
0B
Value of object no. 2
“ATV71HU15M3”
-------
1 byte
1 byte
11 bytes
-------
Id of object no. 3
02
Length of object no. 3
04
Value of object no. 3
“0201”
-------
1 byte
1 byte
0
4 bytes
-------
Id of object no. 4
06
Length of object no. 4
09
Value of object no. 4
“MACHINE 4”
-------
1 byte
1 byte
0
9 bytes
-------
CRC16
Lo
Hi
1 byte
1 byte
• Object no. 1:
Manufacturer name (always "Telemecanique", i.e., 13 bytes).
• Object no. 2:
Device catalog number (ASCII string; for example: “ATV71HU15M3”, i.e., 11 bytes).
The length of this object varies according to drive type. Use the “Length of object no. 2” field to determine the length.
• Object no. 3:
Device version, in "MMmm" format where "MM" represents the determinant and "mm" the subdeterminant (4-byte 
ASCII string; for example: "0201" for version 2.1).
• Object no. 4:
Device name (ASCII string; for example: "MACHINE 4", i.e., 9 bytes).
The length of this object varies according to the device name assigned to the drive (the latter being configured by 
the user): 
[7. DISPLAY CONFIG.]
 menu, 
[7.1 USER PARAMETERS]
 submenu, 
[DEVICE NAME]
 parameter. 
This menu can only be accessed in Expert mode.
Maximum size 16 bytes.