Protect PV.630 Installation and Start-up 
 
80000047963 BAL 
21 of 21 
Isolating Solar Inverters 
The following are required: 
 Multimeter 
  Two-pin voltage detector 
 Circuit diagram 
7.1 Isolation 
Procedure 
 
 
Contact with voltage! 
Risk to life due to electric shock. 
The capacitors can continue to carry voltage for quite 
some time; terminal X11 (AC control cabinet) will also re-
main live.
 
Switching off Q26 (external) and Q4 does not isolate the 
system entirely from the voltage! 
 
The remote signalling lines may still be live even after the 
mains and DC have been disconnected! 
 Only trained skilled personnel may isolate the system. 
 
Do not touch any live parts.
 
 
To isolate the system from the voltage, you must dis-
connect the supply lines.
 
 
Wear personal protective equipment.
 
 Switch the PV solar inverter off via the DOU. 
 Switch off Q26 (external). 
 Switch off F60, F61 (DC/AC control cabinet). 
 Switch off GCBs (external). 
 Remove all F41 fuses (DC/AC control cabinet). 
 Check that there is no voltage at X41 and X3 (DC/AC control 
cabinet). 
 Observe the "five rules of safety", i.e. "earth and short-circuit" 
the AC and DC supplies if necessary. 
 
DANGER