Install Emergency Transfer Units and Associated 
Telephones
Issue 1  September 1995 
9-23
Install Emergency Transfer Units and
Associated Telephones
Emergency transfer capability is provided by a transfer unit mounted on the wall 
next to the trunk/auxiliary cross-connect field.
Analog telephones can be used for emergency transfer. The 500-and 2500-type 
telephones can also be used as normal extensions. Emergency  transfer 
capability may be provided on Central Office (CO) trunks.
The following transfer units are available:
The 808A Emergency Transfer Panel provides emergency trunk bypass 
or power-fail transfer for up to five incoming analog Central Office (CO) 
trunk loops to five selected private branch exchange analog single line 
telephones. When a power failure or other system problem interrupts 
service, the sets are automatically and directly connected to the Central 
Office trunks and are available for emergency use outside the private 
branch exchange service environment.
When a telephone connected to the 808A goes off-hook during bypass, 
circuitry inside the panel places signalling on the Central Office (CO) 
trunk causing the Central Office (CO) to return dial tone. Each 808A 
bypass circuit can be switched to either loop start or ground start 
signalling.
The 574-5 power transfer unit serves up to five power failure transfer 
telephones. The unit provides automatic ground start.
At the cross-connect field, the transfer units are connected to a yellow terminal 
row/connecting block in the trunk/auxiliary field. The units are powered (-48VDC) 
from the EM TRANS RELAY PWR terminals. Refer to Figure 9-6 for pinout 
information. There are seven EM TRANS RELAY PWR terminal pairs to provide 
power to up to seven transfer units.
Install the 808A Emergency Transfer Panel
The 808A is connected to the cross-connect field through a B25A or A25B 