Table 12D Troubleshooting Chart - Noisy System
FAULT
CAUSE
CORRECTIVE ACTION
Noisy 
Operation
- Supply gas problem.  Natural gas pressures 
 should be between 4 inches w.c. and 
 14 inches w.c. LP gas pressures should 
  be between 8 inches w.c. and 14 inches w.c.
 • Refer to Section 6 - Gas Connections for detailed 
  information concerning the gas supply.
- Gas/air mixture problem.
 • Refer to the Gas Valve Adjustment Procedure on 
 
 
 
 
  page 73 of this manual for the proper gas valve setting.  
  Verify that the vent/air intake lengths do not exceed the 
  maximum listed in the General Venting section.
- Dirty/damaged burner.  
 • Refer to page 60 in this manual for the burner removal 
  and inspection procedure. Clean or replace the burner 
 as 
necessary.
- Low water flow through the heat exchanger.  
 • Refer to Section 5 - System Piping for minimum flow 
 rates. 
 
- Air in the piping system.  
 • Properly purge all air from the piping system.
No Pump 
Operation 
- Blown fuse.
 • Replace fuse F5 on the control board, see page 62 of 
 this 
manual. 
- Faulty pump.
 • Replace pump.
- Faulty pump relay.
 • Replace pump relay.
- Internal fault on control board.
 • Replace main control board.
Relief Valve 
Opening
-
 System pressure exceeds relief valve 
 setting.
 • Lower the system pressure below the 150 PSI rating of 
  the supplied relief valve.
       
Installation & Service Manual
TM