63
12  
Troubleshooting 
(continued)
Table 12A Troubleshooting Chart - No Display
FAULT
CAUSE
CORRECTIVE ACTION
No Display
- No 120 VAC supplied to unit.   
•  Check external line switch, fuse, or breaker.
• Check wiring harness connection between display 
  board and main control board. Connect harness at both   
   points.
- Bad display board.  
•  Replace board.
- Bad main control board.  
•  Replace the main control board.
- Blown fuse. 
• Replace fuse F3 on the main control board, see 
 
 
 
 
  
  page 62 of this manual.
No Burner 
Operation
- Tank temperature set point satisfied.
•  Review temperature setting.
- Unit locked out on fault.  
•  Consult display for specific fault. Refer to fault 
  descriptions on page 66 of this manual for corrective 
 actions.
Unit Does 
Not Modulate 
Above 50%
- Flue sensor open.  
•  Verify that the flue sensor is located in the flue outlet.
•  Check wiring connections at the flue sensor.
•  Check the resistance of the flue sensor and compare 
  to Table 12C on page 64 of this manual.
       
Installation & Service Manual