Crown Boiler BWF195 用户手册

下载
页码 54
 
44
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
120 volts across 
black and white 
transformer 
primary leads on 
back of R8285 ? 
Thermostat 
calls for heat
Circulator 
start?
Power off          
Blown fuse or 
tripped breaker 
Miswired or
loose electrical
connection in
120 volt line
120 volts across  
circulator 
connections?
* Loose connection in 
t'stat or zone valve end 
switch wiring
* Defective t'stat or zone 
valve end switch
T'stat or zone system 
miswired-consult zone  
valve or t'stat 
manufacturer's 
instructions.
N
Induced 
draft fan 
start?
120 volts 
present?
24 volts present 
across yellow 
and orange 
connections on 
R8222?
* Boiler off on 
high limit
* Defective 
high limit
Defective 
R8222 relay - 
see note 6 on 
page 43.
* Socket not fully 
seated on relay
Y
Y
N
N
Y
N
Y
 N
START
Y
N
Y
24volts across R 
and C on R8285 
fan center?
* Defective 
transformer. 
Replace R8285. 
See note 5 on 
page 43
24 volts across 
G and C on 
R8285 fan 
center?
* Seized or 
defective 
circulator
  
* Defective relay on 
R8285 - see note 6 on 
page 43
* Relay not fully seated 
in socket
* Loose connection in 
circulator wiring
Unplug fan and 
check for 120 volts 
across black and 
white connections 
on female half of 
plug.
* Loose 
connection at 
fan plug or fan 
capacitor
Defective 
capacitor
* Defective fan
24 volts 
present across 
yellow and 
purple 
connections on 
R8222?
Reconnect fan
* Kinked or blocked 
vacuum switch tubing
* Defective vacuum 
switch
Wait 30-50 
seconds    
(prepurge)
Continued on 
next page
N
Y
N
Y
N
Y
BWF Troubleshooting Chart 
 
Caution: Read page 43 before attempting to use this chart