Crown Boiler BWF195 用户手册

下载
页码 54
 
46
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Does 
spark stop 
when pilot 
lights?
24 volts 
across 
terminals 2&3 
at S8670?
Spark 
across 
ignitor/sensor 
gap?
Y
Can you 
hear 
sparking?
Defective  
S8670 
module
Break in 
spark cable 
insulation
Break in pilot 
porcelain
Incorrect 
pilot spark gap
Loose 
connection in 
spark cable
Loose 
ground 
connection
N
Pilot 
lights?
Y
N
N
Defective 
S8670 module
24 volts 
across PV 
MV/PV at gas 
valve?
Defective EI 
wiring 
harness.
N
Loose connection 
in ignition cable or 
ground wire
Pilot electrode 
porcelain cracked
Pilot flame not 
covering gap 
between electrode 
and grounding 
strap
Low gas pressure 
at gas valve inlet
Defective S8670 
module
Main 
burner 
lights?
N
Y
24VAC 
across 
terminals 1&2 
on S8670?
Y
N
N
Defective
S8670 
module
 24 volts 
between MV 
MV/PV on gas 
valve?
Defective 
gas valve
*Defective EI 
harness
END
START 
(24 volts is present across 5 and 6 on S8670, 30-50 
second prepurge period has passed, but main 
burners do not light)
N
Y
Y
N
Y
Y
Y
* Low line pressure
Plugged, kinked or leaking 
pilot tubing
Plugged pilot orifice
Gas line not purged of air
Defective pilot assembly
Defective gas valve
Intermittent Ignition System Troubleshooting Chart