PROPERTY DAMAGE
.•.Ensure.that.control.center.voltage.and.phase
. match.the.disposer.motor.and.electrical.supply...
. Check.nameplates.on.disposer.and.control..
. center.for.voltage.and.phase.specifications.
.•.Refer.to.the.control.center.wiring.diagrams.in..
. this.manual.for.correct.connection.
.•.Use.NEMA.4.watertight.electrical.connectors..
. (not.supplied).when.making.electrical.connections..
. to.the.control.center.
ELECTRICAL SHOCK
.•.Turn.off.all.electrical.supply.to.the.disposer.before.
attempting.any.work.on.it..Use.a.voltmeter.or..
circuit.tester.to.ensure.that.power.is.off.
.•.All.Installation.work.must.conform.to.local..
plumbing.and.electrical.codes.
.•.All.components.(disposer,.WX,.control.center..
and.solenoids).must.be.carefully.and.permanently.
grounded.
.•.A.properly.fused.disconnect.must.be.installed.at.
the.electrical.supply.source.for.the.control.center.
.•.The.control.center’s.door.disconnect.must.be.in.the..
off.position.before.the.panel.door.can.be.opened..
Power.is.still.present.at.the.disconnect.until.power.
is.turned.off.at.the.electrical.supply.source.
LINE.VOLTAGE
Connect.the.incoming.line.power.to.the.electrical.
disconnect.switch.and.connect.the.disposer.motor.to.
labeled.terminal.blocks.in.the.control.center..Use.the.
appropriate.voltage.and.phase.wiring.diagram(s).in.
the.Wiring.Diagram.section.at.the.end.of.this.manual..
A.wiring.diagram.is.also.located.on.the.inside.door.of.
the.control.center..Wire.the.disposer.motor.for.correct.
voltage.using.the.connection.diagram.inside.the.motor.
terminal.box.
LOW.VOLTAGE
The.WX-101A.control.center.uses.low.voltage.(24.V)..
to.operate.contactor.coils,.solid.state.control.circuit,.
push.buttons,.and.solenoid.valves..Red.wires.denote..
a.24.V.circuit.
COLD.WATER.SOLENOID.VALVE
One.24.V.cold.water.solenoid.valve.is.supplied.with.
control.centers..Connect.solenoid.valve.to.terminals.4.
and.13..Supplied.flow.control.valve.is.to.be.connected.
to.cold.water.line.
Wire.per.local.electrical.code.using.NEMA.4.water-tight
electrical.connections.
HOT.WATER.SOLENOID.VALVE
One.24.V.hot.water.solenoid.valve.is.supplied.with..
control.centers..Connect.solenoid.valve.to.terminals.7.
and.18..No.flow.control.valve.is.to.be.used.on.hot.water.
line..Use.1/2".compression.fitting.to.connect.hot.water.
line.to.Waste.Xpress.
PERSONAL INJURY
Disconnect.electricity.at.line.disconnect.switch.
before.servicing.system.
Electrical Connections