About the Power Module
302764-B Rev 00
1-5
 
AC Input Electrical Requirements
The installation site must meet the electrical requirements for AC power as shown 
in 
 lists the wall receptacle requirements for AC power.
Table 1-4.
Wall Receptacle Requirements for AC Power
 
Table 1-3.
Electrical Requirements for the AC Model
Input Voltage
 
Maximum Input Current
Maximum System Power
180-264 V
50-60 hertz (Hz), +/-3%
14 amperes (A) maximum at 
180 VAC for 
each input
(2 inputs per power unit)
2000 watts (W)
Country
Receptacle
Voltage
United States and 
Canada
National Electrical Manufacturers Association
(NEMA) L6-20R standard receptacle 
180-264 V
Any other country
Your Versalar 15000 distributor attaches the 
necessary plug to the power cable and informs 
you of the receptacle you need.
200-240 V