The BACnet VAV Actuator provides Direct Digital Control (DDC) for Variable Air Volume 
(VAV) terminal box applications. Temperature control varies with the application. If present, 
heating can be provided by hot water, up to three stages of electric reheat, or optional 
baseboard radiation. 
Sequencing Logic (optional) 
This application has the additional capability to sequence the flow and mechanical heating 
when heated supply air is available. 
Control Temperature Setpoints 
The controller maintains a specified temperature setpoint based on Day/Night mode, or the 
heating/cooling mode, or the setpoint dial (if used). 
Day/Night Mode 
The controller maintains the specified day setpoint temperature during daytime hours and the 
specified night setpoint at night. 
Night Mode Override Switch 
If the ROOM TEMPERATURE SENSOR has an override switch, it can be used to command 
the controller into day mode for an adjustable period of time. This only affects a controller in 
night mode. 
Control Loops 
Temperature Loop – Heating Loop  Cooling Loop – maintain temperature setpoint by 
changing the flow setpoint or modulating the heat source (valve/electric heat). 
Flow Loop – maintains flow setpoint by modulating the damper actuator.