Hot Water Reheat 
•   
 
When the controller is in cooling mode, the heating valve(s) are closed. 
The heating loop modulates the heating valve(s) to warm up the room. In cooling mode, the 
heating valve is closed.  
Electric Reheat 
 
CAUTION:  
Verify that the equipment is supplied with safeties by others to ensure that there is 
airflow across the heating coils when they are to be energized. 
The heating loop controls up to three stages of electric reheat to warm up the room. The 
electric reheat is time modulated using a duty cycle. When the controller is in cooling mode, 
the electric heat is OFF at all times. 
Notes 
1.  If the temperature swings in the room are excessive or if there is trouble in maintaining 
the setpoint, contact your local Siemens Building Technologies, Inc. representative for 
more information. 
2.  The BACnet VAV Actuator, as shipped from the factory, keeps all associated equipment 
OFF. The controller and its equipment are released to application control at start-up. 
3.  “Safeties by Others”: This note implies that the associated equipment has safety features 
installed, for example adding mechanical stops to the dampers.  
 
CAUTION:  
Do not set HTG FLOW MIN to 0 cfm (0 lps). A minimum airflow should be provided 
across the heating coils when the heating valve is open.