Klinkmann Automation Omron Ethernet DAServer 
45 
 
 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4                                                                 17014m14  
Memory Area 
Prefix 
Tag 
Type  
Range 
Value 
Range  
Format 
Suffix 
IR & SR areas  
(Bit status)(***) 
IR  
Discrete  
IR0:00...IR255:15 
or 0.00...255.15  
0, 1 
 
IR & SR areas 
(Word contents) (***) 
 IR 
Integer 
IR0...IR255 
or 0...255  
(*) 
u s b f g l 
m d e c 
Latching Relay area  
 (Bit status) 
LR 
Discrete 
LR0:00... LR15:15  
 
0, 1 
 
Latching Relay area  
(Word contents) 
LR 
Integer 
LR0... LR15 
(*) 
u s b f g l 
m d e c 
Holding Relay area  
 (Bit status) 
HR 
Discrete 
HR0:00... HR19:15 
 
0, 1 
 
Holding Relay area  
(Word contents) 
HR 
Integer 
HR0... HR19 
(*) 
u s b f g l 
m d e c 
Auxiliary Relay area  
 (Bit status) 
AR 
Discrete 
AR0:00... AR23:15 
 
0, 1 
 
Auxiliary Relay area  
(Word contents) 
AR 
Integer 
AR0... AR23 
(*) 
u s b f g l 
m d e c 
Completion flags for 
Timers/Counters(**) 
TC 
Discrete 
TC0... TC255 
0, 1 
 
Present Values for 
Timers/Counters 
PV 
Integer 
PV0... PV255 
(*) 
u s b f g l 
m d e c 
Data Memory area 
(Bit status) (****) 
DM 
Discrete 
DM0:0...DM6655:15 
 
0, 1 
  
Data Memory area 
(Word contents) (****) 
DM 
Integer 
DM0... 
DM6655 
(*) 
u s b f g l 
m d e c 
 
Item/point names, corresponding to IR and SR areas, may be without prefix. 
 
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with 
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is 
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999.  Default 
value range for Integer Tag Type is unsigned integer. 
 
(**) Read only 
 
(***) Addresses 50 to 199 in IR & SR area in CPM2A/CPM2C PLCs and 20 to 199 in IR & 
SR area in CPM1/CPM1A/SRM1(-V2) PLCs are read only. 
 
(****) Addresses DM1024 to DM6143 in CPM1/CPM1A PCs and DM2048 to DM6143 in 
CPM2A/CPM2C/SRM1(-V2) PCs are read only. 
 
The following examples show the correct format for item names for C/CPM2x PLCs: 
 
IR2:01   -  CIO area (Bit status), word address 2, bit number 1. 
 211       -    CIO area (Word contents), word address 211. 
   LR62.10 -  Latching Relay area (Bit status), word address 62, bit number 10. 
   DM21    -  Data Memory area (Word contents), word address 21.