Omron ethernet direct dr 170 14 用户手册

下载
页码 70
Klinkmann Automation Omron Ethernet DAServer 
46 
 
 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4                                                                 17014m14  
CQM1 PLCs 
The following table lists the supported item names for the CQM1 PLCs:  
 
Memory Area 
Prefix 
Tag 
Type  
Range 
Value 
Range  
Format 
Suffix 
IR & SR area  
(Bit status) 
IR  
Discrete  
IR0:00...IR255:15 
or 0.00... 255.15 (**) 
0, 1 
 
IR & SR area 
(Word contents) 
 IR 
Integer 
IR0... IR255 
or 0... 255 (**) 
(*) 
u s b f g l 
m d e c 
LR area  
 (Bit status) 
LR 
Discrete 
LR0:00... LR63:15  
 
0, 1 
 
LR area  
(Word contents) 
LR 
Integer 
LR0... LR63 
(*) 
u s b f g l 
m d e c 
HR area  
 (Bit status) 
HR 
Discrete 
HR0:00... HR99:15 
 
0, 1 
 
HR area  
(Word contents) 
HR 
Integer 
HR0... HR99 
(*) 
u s b f g l 
m d e c 
AR area  
 (Bit status) 
AR 
Discrete 
AR0:00... AR27:15 
 
0, 1 
 
AR area   
(Word contents) 
AR 
Integer 
AR0... AR27 
(*) 
u s b f g l 
m d e c 
Completion flags for 
Timers/Counters(***) 
TC 
Discrete 
TC0... TC511 
0, 1 
 
Present Values for 
Timers/Counters 
PV 
Integer 
PV0... PV511 
(*) 
u s b f g l 
m d e c 
DM area 
(Bit status) 
DM 
Discrete 
DM0:0...DM6655:15 
 
0, 1 
  
DM area 
(Word contents) 
DM 
Integer 
DM0...DM6655 
(*) 
u s b f g l 
m d e c 
EM area 
(Bit status) 
EM 
Discrete 
EM0:0...EM6143:15 
 
0, 1 
  
EM area 
(Word contents) 
EM 
Integer 
EM0...EM6143 
(*) 
u s b f g l 
m d e c 
 
Item/point names, corresponding to IR and SR areas, may be without prefix.  
 
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with 
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is 
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999.  Default 
value range for Integer Tag Type is unsigned integer. 
 
(**) Represented memory area available in CQM1H-CPU61 CPU. 
  
(***) Read only 
 
The following examples show the correct format for item names for CQM1 PLCs: 
 
   IR2:1          - 
 IR Input area (Bit status), word address 2, bit number 1.