National Instruments cFP-DO-403 用户手册

下载
页码 15
[c]FP-DO-403
10
ni.com
Caution
For Zone 2 applications, install a protection 
device across the external power supply and the COM 
terminal. The device must prevent the external power 
supply voltage from exceeding 42 V if there is a transient 
overvoltage condition.
Special Conditions for Hazardous Locations Use in Europe
The [c]FP-DO-403 has been evaluated as EEx nC IIC T4 
equipment under DEMKO Certificate No. 03 ATEX 0251502X. 
Each module is marked 
 II 3G and is suitable for use in Zone 2 
hazardous locations.
Specifications
These specifications are typical for –40 to 70 °C unless otherwise 
noted. Specifications are subject to change without notice.
Output Characteristics
Number of channels.......................... 16
Output type ....................................... Sinking
Voltage range .................................... 5 to 30 VDC
Output impedance............................. 0.12 
Ω
(0.12 V drop at 1 A)
Maximum current
Per channel ................................. 2 A
All channels
FP-DO-403........................... 16 A
2
cFP-DO-403......................... 16 A
2
  at  –40 to 60  °C
12 A
2
 at 60 to 70 °C
Maximum OFF state leakage............ 50 
μA
Output delay time ............................. 50 
μs
Physical Characteristics
Indicators .......................................... Green POWER and 
READY indicators, 16 green 
output state indicators
Weight
FP-DO-403 ................................. 140 g (4.8 oz)
cFP-DO-403 ............................... 110 g (3.7 oz)