National Instruments cFP-DO-403 用户手册

下载
页码 15
© National Instruments Corp.
9
[c]FP-DO-403
Do not use the [c]FP-DO-403 as the only isolating barrier 
between human contact and working voltages higher than 
250 V
rms
.
Operate the [c]FP-DO-403 only at or below Pollution 
Degree 2. Pollution Degree 2 means that only nonconductive 
pollution occurs in most cases. Occasionally, however, a 
temporary conductivity caused by condensation must be 
expected.
Operate the [c]FP-DO-403 at or below Measurement 
Category II. Measurement Category II is for measurements 
performed on circuits directly connected to the low-voltage 
installation. This category refers to local-level distribution, 
such as that provided by a standard wall outlet.
Safety Guidelines for Hazardous Locations
The [c]FP-DO-403 is suitable for use in Class I, Division 2, Groups 
A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC 
T4 and Ex nA IIC T4 hazardous locations; and nonhazardous 
locations only. Follow these guidelines if you are installing the 
[c]FP-DO-403 in a potentially explosive environment. Failing to 
follow these guidelines may result in serious injury or death.
Caution
Make sure that all products you use in hazardous 
locations are certified for such use. Refer to the product 
label or visit 
ni.com/certification
, search by model 
number or product line, and click the appropriate link in 
the Certification column.
Caution
Do not disconnect I/O-side wires or connectors 
unless power has been switched off or the area is known 
to be nonhazardous.
Caution
Do not remove modules unless power has been 
switched off or the area is known to be nonhazardous.
Caution
Substitution of components may impair 
suitability for Class I, Division 2.
Caution
For Zone 2 applications, install the FieldPoint 
system in an enclosure rated to at least IP 54 as defined 
by IEC 60529 and EN 60529.