National Instruments cFP-DO-403 用户手册

下载
页码 15
[c]FP-DO-403
2
ni.com
2. Align the FP-DO-403 alignment slots with the guide rails on 
the terminal base.
3. Press firmly to seat the FP-DO-403 on the terminal base. When 
the module is firmly seated, the terminal base latch locks it into 
place.
Figure 1.  Installing the FP-DO-403
Installing the cFP-DO-403
The cFP-DO-403
 
mounts on a Compact FieldPoint backplane 
(cFP-BP-x), which provides operating power to the module. 
Installing the cFP-DO-403
 
onto a powered backplane does not 
disrupt the operation of the bank.
To install the cFP-DO-403, refer to Figure 2 and complete the 
following steps:
1. Align the captive screws on the cFP-DO-403
 
with the screw 
holes on the backplane. The alignment keys on the 
cFP-DO-403
 
prevent backward insertion.
2. Press firmly to seat the cFP-DO-403
 
on the backplane.
3. Using a number 2 Phillips screwdriver with a shank of at least 
64 mm (2.5 in.) length, tighten the captive screws to 1.1 N
⋅ m 
(10 lb
⋅ in.) of torque. The nylon coating on the screws prevents 
them from loosening.
1
I/O Module
2
Terminal Base
3
Alignment Slot
4
Key
5
Latch
6
Guide Rails
1
3
2
4
5
6