loads on the output channels, up to 2 A per channel.
1
 Connect 
the external power supply to multiple V and V
SUP
 terminals and 
to multiple C and COM terminals as needed to ensure that the 
maximum current through any terminal is 2 A or less.
Install a 2 A maximum, fast-acting fuse (F2A 250V) between the 
external power supply and the V
SUP
 terminal on each channel. 
Install a 2 A maximum, fast-acting fuse suitable for the load at the 
V
OUT
terminal. Figure 3 shows fuses where appropriate.
Table 1 lists the terminal assignments for the signals associated 
with each channel. Terminal assignments and wiring diagrams are 
also listed on the side panel of the cFP-DO-403 and under the 
slide-in card on the front of the FP-DO-403 module.
National Instruments recommends that you wire the external 
power supply to multiple V
SUP
shows how to connect two output channels to loads.
Wiring for Low-Current Applications
If your application requires 2 A or less combined current through 
all channels of the [c]FP-DO-403, you can wire your application 
as shown in Figure 3. Install a 2 A maximum, fast-acting fuse 
(F2A 250V) between the external power supply and the V terminal 
as shown.
1  
Refer to the 
 an
 sections for the maximum 
output current level on all channels.
Table 1.  Terminal Assignments
Channel
Terminal Numbers
Channel
Terminal Numbers
VOUT
VSUP
COM
VOUT
VSUP
COM
0
1
17
18
8
9
25
26
1
2
17
18
9
10
25
26
2
3
19
20
10
11
27
28
3
4
19
20
11
12
27
28
4
5
21
22
12
13
29
30
5
6
21
22
13
14
29
30
6
7
23
24
14
15
31
32
7
8
23
24
15
16
31
32