National Instruments cFP-PWM-520 用户手册

下载
页码 19
FP-PWM-520 and cFP-PWM-520
14
ni.com
Mechanical Dimensions
Figure 5 shows the mechanical dimensions of the FP-PWM-520 
installed on a terminal base. If you are using the cFP-PWM-520, 
refer to your Compact FieldPoint controller user manual for the 
dimensions and cabling clearance requirements of the Compact 
FieldPoint system.
Figure 5.  FP-PWM-520 Mechanical Dimensions
Power Requirements
Power from network module ............ 1 W
Isolation Voltage
Isolation voltage is verified by a dielectric withstand test.
Channel-to-ground isolation
Continuous ................................. 250 V
rms
, Measurement 
Category II
Dielectric withstand.................... 2,300 V
rms
, 5 s max
Channel-to-channel isolation ............ None
Environmental
FieldPoint modules are intended for indoor use only. For outdoor 
use, they must be mounted inside a sealed enclosure.
Operating temperature ...................... –40 to 70 °C
Storage temperature .......................... –55 to 85 °C 
Humidity ........................................... 10 to 90% RH, 
noncondensing
Maximum altitude............................. 2,000 m
Pollution Degree ............................... 2
109.5 mm
(4.31 in.)
91.44 mm
(3.60 in.)
107.19 mm
(4.22 in.)