temperature calibration modes (E
 
Internal Temperature Calibration 
• 
I appears on right side of screen 
• 
The top left number (77 in example) is the current reading according to the temperature sensor 
• 
The top right number (14 in example) is the current offset (represents 1.4) 
• 
These numbers can change while this screen is displayed even though the primary temperature 
does not change; they are floating point calculations. 
1)  Tap Up or Down arrows to adjust the displayed temperature to match the calibrated source 
i.  Each press results in a 1
°
 F (0.5
°
 C) change 
ii.  The calculation using example numbers below is 78 = 77 + 1.4 
iii.  The offset range is from –10 to +10 actual °s 
 
 
 
Humidity Calibration Mode 
1)  Once in Setup Mode for temperature calibration (step 1 above), tap Mode button to step between 
temperature calibration and humidity calibration 
2)  Press the Up or Down arrow to select the current humidity level 
• 
The top left number (40 in example) is the current reading according to the humidity sensor 
• 
The top right number (-92 in example) is the current offset (represents -9.2) 
• 
These numbers can change while this screen is displayed even though the primary humidity level 
does not change. they are floating point calculations 
o
 
Each press results in a 1% humidity change 
o
 
The calculation using example numbers below is (31 = 40 – 9.2) and 42 = 40 + 1.7 
o
 
The offset is from -10 to +10 
3)  Press the MODE button to calibrate the external temperature sensor or press Program to exit 
calibration mode 
     
 
 
External Temperature Calibration 
• 
If you are using a Waterproof Temperature Sensor, use this mode to calibrate its external 
temperature readings 
• 
E appears on right side of screen 
1)  Tap Up or Down arrows to adjust the displayed temperature to match the calibrated source 
i.  Each press results in a 1
°
 F (0.5
°
 C) change 
ii.  The calculation using example numbers below is 78 = 77 + 1.4 
iii.  The offset range is from –10 to +10 actual °s 
iv.  If no external sensor is installed, EE will be displayed instead