Puls UC10.242 DIN-Rail UPS 规格指南
UC10.241, UC10.242
UC-Series
24V,
15A,
C
APACITOR
-
BASED
B
UFFER
M
ODULES
4. O
UTPUT
The output section of the buffer module is fully controlled and is equipped with an electronic current limitation. A
current overloading of the buffer module cannot happen, independent of which sizes of power supplies are used on
the input of the buffer module.
current overloading of the buffer module cannot happen, independent of which sizes of power supplies are used on
the input of the buffer module.
The current limitation works in a switching mode which reduces the power losses and heat generation to a minimum.
Output in normal mode:
In normal mode (and also in charging mode), the output voltage is slightly lower as the input voltage. The output
voltage follows the input voltage reduced by the input to output voltage drop.
voltage follows the input voltage reduced by the input to output voltage drop.
Input to output voltage drop
max.
0.3V
0.45V
0.45V
at 10A output current
at 15A output current, see Fig. 4-1
at 15A output current, see Fig. 4-1
Ripple & noise voltage
max.
30mVpp
at 20Hz to 20MHz, 50Ohm measurement. This figure
indicates the ripple & noise voltage which is produced
by the buffer module. It can be higher if the supplying
source has a higher ripple and noise voltage.
indicates the ripple & noise voltage which is produced
by the buffer module. It can be higher if the supplying
source has a higher ripple and noise voltage.
Output current
nom.
15A
continuously allowed for the entire voltage range
Output power
nom.
360W
at 24V
Overload behavior
continuous current see Fig. 4-2
Current limitation
typ.
min.
min.
16A
15A
15A
Short-circuit current
min. 17.9A
load
impedance 100mOhm, see Fig. 4-2
max.
21.0A
load impedance 100mOhm, see Fig. 4-2
Output capacitance
typ.
1 500μF
included inside the buffer module
Capacitive and inductive loads
No
limitation
Output in buffer mode:
The output voltage is fully regulated in buffer mode.
The unit switches into buffer mode, when the input voltage falls below the transfer threshold input voltage level, The
buffer voltage is slightly lower than this threshold input voltage. The unit switches back to normal mode, as soon as
the input voltage exceeds the transfer threshold voltage, which is specified in the input section.
buffer voltage is slightly lower than this threshold input voltage. The unit switches back to normal mode, as soon as
the input voltage exceeds the transfer threshold voltage, which is specified in the input section.
Output voltage
typ.
22.45V
±1%
22.25V
±1%
22.12V
±1%
at no load
at 10A buffer current
at 15A buffer current
at 10A buffer current
at 15A buffer current
Ripple & noise voltage
max.
30mVpp
at 20Hz to 20MHz, 50Ohm measurement
Output current
nom.
15A
continuously allowed
Output power
nom.
360W
at 24V
Overload behavior
continuous current see Fig. 4-2
Current limitation
typ.
min.
min.
16A
15A
15A
Short-circuit current
min.
17.9A
load impedance 70mOhm, see Fig. 4-2
max.
21.0A
load impedance 50mOhm, see Fig. 4-2
Capacitive and inductive loads
No
limitation
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC)
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/27