Cisco CATALYST 6500 2500 WATT AC POWER SUPPLY 规格指南

下载
页码 9
wattage power supply 
with redundancy 
enabled 
The system power equals the power 
capability of one supply.  
There is no change in the module 
status because the power capability is 
unchanged. 
Insertion of equal-
wattage power supply 
with redundancy 
disabled 
System log and syslog messages are 
generated. 
The system power is the combined 
power capability of both supplies.  
The modules that are marked as 
power-deny
 in the 
Status
 field of 
the show module command output 
are brought up, if there is sufficient 
power. 
Insertion of higher-
wattage power supply 
with redundancy 
enabled 
System log and syslog messages are 
generated. 
The system disables the lower-
wattage power supply. The higher-
wattage supply powers the system.  
Insertion of lower-
wattage power supply 
with redundancy 
enabled 
System log and syslog messages are 
generated. 
The system disables the lower-
wattage power supply. The higher-
wattage supply powers the system. 
Insertion of higher- or 
lower-wattage power 
supply with redundancy 
disabled 
System log and syslog messages are 
generated. 
The system power is increased to the 
combined power capability of both 
supplies. 
The modules that are marked as 
power-deny
 in the 
Status
 field of 
the show module command output 
are brought up, if there is sufficient 
power. 
Removal of power 
supply with redundancy 
System log and syslog messages are 
generated. 
If the power supplies are of equal 
wattage, there is no change in the 
module status because the power 
capability is unchanged. 
If the power supplies are of unequal wattage 
and the lower-wattage supply is removed, 
Page 3 of 9
Cisco - Power Management for Catalyst 6000 Series Switches
5/2/2006
http://www.cisco.com/warp/customer/473/142.html