Redline Communications Inc. SC1000E 用户手册
User
BASE
STATION
Manual
Doc #70-00100-01-00-DRAFT
Proprietary Redline Communications © 2009
Page 47 of 60
January 7, 2009
Input Protection:
Transient protection
Mains fuse in both lines
Disconnect above 300 VAC
DC Output
Nominal output:
Nominal output:
53.5 VDC
Float/Boost range:
48 – 57.6 VDC
Standby test range:
43.5 – 48 VDC
Output Power:
800 W at nominal input / 350W at 85 VAC
Maximum Current:
16.7 Amps at 48 VDC and nominal input
Current Sharing:
±5% from true average current between modules
Static voltage regulation:
±1.0% from 5% to 100% load
Dynamic voltage regulation: ±5.0% for 25-100% load variation, regulation time < 10 ms
Hold up time:
Hold up time:
> 20 ms; output voltage > 43.0 VDC at 80% load
Ripple and Noise:
< 100 mV peak to peak, 20 MHz bandwidth
< 2 mV RMS psophometric
Output Protection:
Overvoltage shutdown
Blocking
diode
Short circuit proof
High temperature protection
DC Output
Efficiency:
Efficiency:
Typ. 91% at 60-100% load
Isolation:
3.0 KVAC – input and output
1.5 KVAC – input earth
0.5 KVDC – output earth
Alarms:
Low mains shutdown (<85 VAC)
High temperature shutdown
Rectifier
Failure
Overvoltage shutdown on output
Low voltage alarm at 43.0V
CAN bus failure
Warnings: Rectifier
in power derate mode
Remote battery current limit activated
Input voltage out of range, flashing at overvoltage
Loss of CAN communication with control unit, stand alone mode
Visual indications:
Green LED: ON, no faults
Red LED: rectifier failure
Yellow LED : rectifier warning
Operating temp:
-40 to 75 C (-40 to 167°F)
Derating above 55 C linear to 450W at +65 C
Storage temp:
-40 to 80 C (-40 to +176°F)
Cooling:
1 fan (front to back airflow)
Fan Speed:
Temperature and current regulated
MTBF:
> 300, 000 hours Telcordia SR-332
Issue I, method III (a) (T ambient : 25°C)
Acoustic Noise:
< 45 dBA at nominal input and full load
Humidity Operating:
5% to 95% RH non-condensing
Storage:
0% to 99% RH non-condensing
Dimensions:
42.5 x 88.9 x 250 mm (1.67 x 3.5 x 9.84”) (W x H x D)
Weight 1.08 kg (2.38 lbs)
AC Input
Voltage:
Voltage:
2 x AC feeds (85-300 VAC 1 ph)
Frequency:
45 to 66 Hz
Surge protection:
Internal fuses (L & N)
Disconnect above 300 VAC
Monitoring
Local operation:
Local operation:
Menu driven software via keypads and LCD or PC
Remote operation: Eltek PowerSuite via modem or Monitoring via Eltek WebPower (WEB
Interface, SNMP protocol and email)