Power Requirements 
The DC wide mouth power supply supports from -18 VDC to -60 VDC. The optional AC 
power supply is auto-sensing in the 90 to 132 V and 180 to 264 V ranges.  
Table 38: Spec.: RedMAX 4C Power Dissipation (Watts) 
 
Sectors without 
Redundancy 
Sectors with Redundancy 
& Diversity 
Modules 
1 3 4 6 1 3 4 6 
BBM 
50 150 200 300 100 200 300 400 
TCM 
30 30 30 30 60 60 60 60 
Cooling 
Module 50 50 50 50 
100 
100 
100 
100 
RRH 
150 450 600 900 150 450 600 900 
Total 
280  680  880 1280 410  810 1060 1460 
 
7.6 
Heat dissipation (Shelf) 
Table 39: Spec.: Heat Dissipation for SC-1000 Shelf (IDU) in BTU/Hour 
 
Sectors without 
Redundancy 
Sectors with Redundancy 
& Diversity 
Modules 
1 3 4 6 1 3 4 6 
BBM 
170  510  680 1020 340  680 1020 1360 
TCM 
100 100 100 100 200 200 200 200 
Fan 
Tray 
(CU)  170 170 170 170 170 170 170 170 
Total 
440 780 950 1290 710 1050 
1390 
1730 
 
7.7 
Heat dissipation (Remote Radio Head) 
Table 40: Spec.: Heat Dissipation for RRH (ODU) in BTU/Hour 
 
Sectors without 
Redundancy 
Sectors with Redundancy 
& Diversity 
Modules 
1 3 4 6 1 3 4 6 
RRH 
400 1200 1600 2400 400 1200 1600 2400 
Total 
400 1200 1600 2400 400 1200 1600 2400